Installation example
The new Cibin R455 monoblock range
Ultra-low GWP refrigerants
The new Cibin monoblock range use the latest generation ultra-low GWP refrigerants. With a GWP of only 146, R455A is the definitive solution for future low/medium temperature commercial and industrial refrigeration.
After multiple tests and studies based on the entire cold chain, it has been shown that the TEWI (Total equivalent warming impact) of machines operating with R455A is significantly lower thanks both to the refrigerant, COP and the ease of managing the machines, which are more user-friendly compared to old R404A machines
The refrigerant used is composed of a mildly flammable azeotropic mixture (A2L in accordance with ISO 817). However, the use of R455A is made safe (in compliance with the principal safety standards) due to the specific flammability properties of the refrigerant, which include:
a) Relatively high lower flammability limit equal to 11,8% (LFL);
b) Relatively low upper flammability limit compared to the low flammability limit 12,9% (UFL);
c) Minimum ignition energy more than 1000 times higher than propane;
d) Flame propagation speed lower than 1,5cm/s.
Technical characteristics:
Configurazione standard
• Sealed circuit
• Hermetic compressor
• Electronic fans
• Anti-vibration compressor brackets
• Air condensation
• Galvanized powder coated sheet steel body
• Evaporator body of aluminium-magnesium alloy
• Evaporator of copper pipes and aluminium fins
• Condenser of copper pipes and aluminium fins
• Automatic restarting low pressure switch (to be welded)
• Automatic restarting high pressure switch
• Compressor timer management to avoid too near start-ups
• Axial fan
• Condensation control device *
• Thermic compressor protection
• General magnete-thermal protection
• Thermostatic expansion valve with external equalization *
• Suction pressure relief valve (only for low temperature models)
• Dehydrator filter
• Suction-side liquid separator *
• Defrost hot gas solenoid valve
• Automatic hot gas defrosting
• Condensation outlet siphon
• Condensation outlet resistor (only for low temperature models)
• Cold room ceiling light and power source cable with related protection via fuse
• Ambient temperature probe
• Defrosting end temperature probe
• Condensation control temperature probe*
• Connecting cable for door resistor with protection 4A fuse
(only for low temperatures models) and related protection with fuses
• Connecting cable for door micro switch to turn off the system and to turn on the light at door opening
• Transformer
• Digital display with temperature indicator at one decimal
• On/Off switch
• Cold room light switch
• Running state display: cold – defrosting – evaporator fans – alarm status
• Programming keys
• Alarm display
• Manual defrosting key
• Acoustic alarm
• High temperature alarm
• Low temperature alarm
• High temperature alarm dirty condenser
• Low temperature alarm condenser
• Open door alarm
• High pressure alarm
• Defrosting end alarm because of time-out
• Alarm ambient temperature probe defect
• Alarm defrosting end temperature probe defect
• Alarm condensation control temperature probe defect
• Timer emergency running in case of these events:
– Ambient temperature probe defect
– Defrosting end temperature probe defect
– Condensation control temperature probe defect
– Cold room door open (if there is door micro switch)
• Pre-set connection for Frigotel® supervision
Optional:
- • • Door micro switch
• Voltage display for machine stop in case of incorrect power supply
• Acoustic siren with flashing to indicate the alarm state
• Electronic module for the connection to Frigotel® supervision system
* depending on model
Destined use
Destined use, intended and unintended uses
Cibin’s refrigerating equipment is classed as food and agricultural machinery (MACHINES DIRECTIVE 2006/42/EC), destined for the treatment
of food products.
The machine is designed for the conservation of foods and/or “fresh” products at temperatures indicated in annexes.
It has been designed to work in ambient temperatures from +16°C to +43°C (class T).
It has been designed to maintain a set temperature in a refrigerated cold room suitable for such uses.
The machine is not designed for use in cold rooms situated outside.
The machine is not designed for installation and use in an environment where there is risk of explosion.
Any use other than that permitted shall be considered improper, and in this case the Manufacturer will decline all liability.
The machine is not designed for the conservation of products, which produce corrosive substances.
Models
R455A
R455A – 50Hz – TN
R455A – 50Hz – BT
R455A – 50Hz – TN – W
R455A – 50Hz – BT – W
* Max Temperatura ambiente: + 43°C
Ta: Temperatura ambiente
Tc: Temperatura cella